Chloridos Advance
The ChloriDos™ system accurately generates, doses and monitors Chlorine Dioxide into water services. It is used to disinfect water and control legionella and other potentially harmful pathogens.
The ChloriDos™ generates in situ, within a safe, self contained reactor unit, Chlorine Dioxide concentrates between 1% and 5% either by acid/chlorite method or stabilised Chlorine Dioxide pre cursor and activator. The Chlorine Dioxide solution is then further diluted into a motive water stream and injected into the process on site. Installations are typically either recirculated via a water storage tank or rising main.


|
ChloriDos Model |
Product Description |
Typical ClO2 g/h production |
|
CDS-AD2E-120-300 |
ChloriDos Advance System (electronic pumps) |
2 – 300 g/h |
|
CDS-AD2E-240-600 |
ChloriDos Advance System (electronic pumps) |
5 – 600 g/h |
|
CDS-AD2D-100-250 |
ChloriDos Advance System (digital pumps) |
2 - 250 g/h |
|
CDS-AD2D-220-550 |
ChloriDos Advance System (digital pumps) |
5 – 550 g/h |

Water storage tank

Rising main
General Technical Data
- Conex Dia 1 analyser/controller

- Aquacell with hydro mechanical cleaning
- Measuring range 0-50mg/l ClO2
- Analogue or digital water meter inputs
- Water meter overdose protection
- Volt free outputs for connection to BMS systems
- Remote alarm terminals
- Internal contactor for circulation pump connection (pump optional)
- Safety flow sensors in sample and dilution flows
- Sight glass for visual ClO2 indication
- Max operating pressure 6 Bar (sample cell 3 Bar)
- Enclosed reactor with flush facility
- Superior build quality for trouble free operation
Back Board Hole Centres
Conex Technical Data
|
Electronics |
16 bit microprocessor system |
Limit Values |
Adjustable to physical variable within measuring range |
|
Display |
High resolution plain text LCD with back light |
Hysteresis |
0 to 50% of the upper limit of the measuring range |
|
Relay Outputs |
1 alarm relay 2 controller relays (230V ,6A, max 550VA) |
Set Point selection |
0 to 100% of measuring range |
|
Signal Outputs |
4 analogue (4-20mA) outputs galvanically isolated from the inputs, max load 500 Ohm |
Proportional Band (Xp) |
0.1 to 3000% |
|
Temperature compensation |
Manually or automatically from temperature sensor (fitted) |
Reset time (Tn) |
1 to 3000s resolution 1s |
|
Calibration |
With plausibility check |
Deriv action time (Tv) |
1 to 3000s resolution 1s |
|
Admissable temperature |
Operation: 0 to 50⁰C Storage: -22 to 65⁰C |
On time |
0.1 to 10s |
|
Relative Air Humidity |
Max 90% at 40⁰C (not condensing) |
Constant load |
0 to 50% |
Technical Data
|
Mains supply |
230V ±10% 50Hz 30mA RCBO protection recommended (6A) |
Pipe connections |
1/2 “ PVC unions |
|
Power Consumption |
450 W |
Dosing concentration |
2 – 5% |
|
Aux Power |
Rated 2A at 230V |
Environmental protection level |
IP65 |
|
General alarm output |
Rated 6A at 230V (resistive) |
Back board dimensions |
976 x 1100mm |
|
Water meter inputs |
Digital or analogue (4-20mA) |
Terrain dimensions |
1200 x 1600 x 650mm |
|
Optional circulation pump |
Recommended Grundfos CHN2-20 or alternative pump max 0.37kW |
Weight |
Back board 45kg approx Terrain 195kg approx |
|
Max operating pressure |
6 Bar |
All ChloriDos™ systems are supplied fully wet/pressure tested to 6 Bar (ClO2 reaction vessels 15 Bar), with fully configured control software, completed operational diagnostic checks, unique ID serial numbers and full documentation.