Chloridos Mini - Lite Analyser Upgrade

The ChloriDos™ Upgrade allows your existing ChloriDos™ Mini / Lite system to monitor accurately the residual Chlorine Dioxide in the controlled process. 
 
The Upgrade offers a unique ‘boost’ feature to maintain disinfection levels during low flow periods so maintaining residual Chlorine Dioxide levels in the process.  It can also suspend dosage at high residual levels as a further safety feature.
 
The upgrade Analyser can be utilised alongside the ChloriDos™ Batch Unit to control process pumps and monitor an individual process 
 
Chlorine Dioxide generation, dosing and monitoring

General Technical Data

  • Conex Dia 1 analyser/controller
  • Aquacell with hydro mechanical cleaning
  • Measuring range 0-10 mg/l ClO2
  • Analogue or digital water meter inputs
  • Water meter overdose protection
  • Unique Boost feature to maintain disinfection levels during low flow periods
  • Safety flow sensor in sample flow
  • Volt free outputs for connection to BMS systems
  • Sample cell max operating pressure 3 Bar
  • Remote alarm terminals
  • 4-20mA scalable analogue outputs for ClO2 and temperature
  • Superior build quality for trouble free operation

All ChloriDos™ Analysers are supplied fully wet/pressure tested to 3 Bar with fully configured control software, completed operational diagnostic checks, unique ID serial   numbers and full documentation.

ChloriDos™ Model

Product Description

CDS-UPGRADE

Conex Dia 1 compact (c/w connections for ChloriDos™)

Conex Technical DataConex controller

 Mains supply

230V ±10% 50Hz 30mA RCBO protection recommended (6A)

Electronics

16 bit microprocessor system

Display

High resolution plain text LCD with back light

Relay Outputs

1 alarm relay

2 controller relays  (230V ,6A, max 550VA)

 

 Signal Outputs

4 analogue (4-20mA) outputs galvanically isolated from the inputs, max load 500 Ohm

Proportional Band (Xp)

0.1 to 3000%

Temperature compensation

Manually or automatically from temperature sensor (fitted)

Reset time (Tn)

1 to 3000s resolution 1s

Calibration

With plausibility check

Deriv action time (Tv)

1 to 3000s resolution 1s

Admissable temperature

Operation: 0 to 50⁰C

Storage: -22 to 65⁰C

On time

0.1 to 10s

Relative Air Humidity

Max 90% at 40⁰C

(not condensing)

Constant load

0 to 50%

Limit Values

Adjustable to physical variable within measuring range

Environmental protection level

IP65

Hysteresis

0 to 50% of the upper limit of the measuring range

Back board dimensions

495 x 495 mm

Set Point selection

0 to 100% of measuring range

Weight

5 kg

 

 Signal Outputs

4 analogue (4-20mA) outputs galvanically isolated from the inputs, max load 500 Ohm

Proportional Band (Xp)

0.1 to 3000%

Temperature compensation

Manually or automatically from temperature sensor (fitted)

Reset time (Tn)

1 to 3000s resolution 1s

Calibration

With plausibility check

Deriv action time (Tv)

1 to 3000s resolution 1s

Admissable temperature

Operation: 0 to 50⁰C

Storage: -22 to 65⁰C

On time

0.1 to 10s

Relative Air Humidity

Max 90% at 40⁰C

(not condensing)

Constant load

0 to 50%

Limit Values

Adjustable to physical variable within measuring range

Environmental protection level

IP65

Hysteresis

0 to 50% of the upper limit of the measuring range

Back board dimensions

495 x 495 mm

Set Point selection

0 to 100% of measuring range

Weight

5 kg

Analyser Upgrade Package Contents

  • Conex Dia 1 compact
  • Pressure loading valve kit
  • Wall mounting kit
  • 6/12 sample line
  • Sample isolator valve assembly
  • Jaco fittings for sample line
  • Full installation instruction including wiring instructions for connection to ChloriDos™ Lite or Mini
  • Full installation instructions for connection to ChloriDos™ Batch Unit

Optional extras

  • 10” sample line filter bowl kit
  • 10” 20 micron washable filter
  • Spin down sediment trap 3/4” uPVC filter assembly 104 micron
  • Tmac remote monitoring system

Sample cell Sample cell with measuring electrode and reference probe